الاثنين، 20 يناير 2020

Electrical Machines Lab -OC & SC TEST ON 1–PHASE TRANSFORMER.

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&


  Electrical And Electronics Engineering 



OC & SC TEST ON 1–PHASE TRANSFORMER.




The difficulties in testing of large transformers by direct loading 
(I) large amount of energy has to be wasted in such test
 (ii) it is a stupendous (impossible for large transformers) task to arrange a load large enough for direct loading. 




Thus performance characteristics of a transformer must be computed from a knowledge of its equivalent circuit parameter which, in turns, are determined by conducting simple tests involving very little power consumption, called no loading test. In these tests the power consumption is very small. The two-non loading tests are (I) open circuit test (ii) short circuit test. These two tests help to determine (1) the parameters of equivalent circuit (2) predetermine voltage regulation (3) pretermine efficiency.

Open Circuit  Test :


As the name suggests, the secondary is kept open circuited and nominal value of the input voltage is applied to the primary winding and the input current and power aremeasured. In Fig. V,A,W are the voltmeter, ammeter and wattmeter respectively.

Let these meters read V1, I0 and W0 respectively.Fig. shows the equivalent circuit of the transformer under this test. The no load current at rated voltage is less than 1 percent of nominal current and hence the loss and drop that take place in primary impedance r1 +jxldue to the no load current I0 is negligible. The active component Ic of the no load current Irepresents the core losses and reactive current Im is the current needed for the magnetization.

Thus the watt meter reading The parameters measured already are in terms of the primary. Sometimes the pri- mary voltage required may be in kilo-Volts and it may not be feasible to apply nominal
voltage to primary from the point of safety to personnel and equipment. If the secondary
voltage is low, one can perform the test with LV side energized keeping the HV side open
circuited. In this case the parameters that are obtained are in terms of LV . These have to
be referred to HV side if we need the equivalent circuit referred to HV side.

Sometimes the nominal value of high voltage itself may not be known, or in doubt,especially in a rewound transformer. In such cases an open circuit characteristics is firstobtained, which is a graph showing the applied voltage as a function of the no load current.This is a non linear curve as shows  This graph is obtained by noting the currentdrawn by transformer at different applied voltage, keeping the secondary open circuited. Theusual operating point selected for operation lies at some standard voltage around the kneepoint of the characteristic. After this value is chosen as the nominal value the parametersare calculated as mentioned above.

Short Circuit Test
The purpose of this test is to determine the series branch parameters of the equiv-
alent circuit of Fig.. As the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. Let these values be Vsc, Isc and Wsc respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation current which is only 1 percent or less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. Also I1 = I2 as I0 0. 

Therefore Wsc is the sum of thecopper losses in primary and secondary put together. The reactive power consumed is thatabsorbed by the leakage reactance of the two windings.

If the approximate equivalent circuit is required then there is no need to separate r1
and r2 or xl1 and xl2. However if the exact equivalent circuit is needed then either r1 or r2  is determined from the resistance measurement and the other separated from the total.

As for the separation of xl1 and xl2 is concerned, they are assumed to be equal. This is a fairly valid assumption for many types of transformer windings as the leakage flux paths are hrough air and are similar.
Source : Nptel

Do not Delete prevent copying

Self Learners By Maniramakrishna

المشاركات الشائعة

Comments

Loom solar

Email subscribe

Enter your email address:

Delivered by FeedBurner

Loom solar 2