Monday, 20 January 2020

Electrical Machines Lab-SUMPNER’S TEST ON PAIR OF SINGLE PHASE TRANSFORMERS.

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&
  Electrical And Electronics Engineering 

SUMPNER’S TEST ON PAIR OF SINGLE PHASE TRANSFORMERS.




To perform sumpner’s test n  pair of identical 1- phase transformers to find the full load copper losses & iron losses of transformers.

 From test results calculate 
1) Equivalent parameters. 
2) Percentage Efficiency 
3) Percentage r egulation at given power factor & loads.

THEORY
            While OC and SC tests on a transformer gives its equivalent circuit parameters. These can not be used for the heat run test where the purpose is to determine the steady temperature rise if the transformer was fully loaded continuously this is so because under each of these tests the power loss to which the transformer is subjected is either the core loss or copper loss but not both. The way out of this impasse with out conducting an actual loading t est is sumpner’s test which can only be conducted simultaneously  on two identical transformers. In conducting the sumpner’s test  the primaries of the two transformers are connected in parallel across the rated voltage supply (V1), while the two secondaries are connect ed in phase opposition as in fig. Current at low voltage (V2) is injected in to secondaries to rated value.



for more ..........


            As per superposition theorem, if V2 source is assumed shorted the two transformers appear in open circuit to source V1 as their secondaries are in phase opposition and therefore no current can flow in them. The current drawn from sorce V1 is thus 2Io (twice the no load current of each transformer) and power is 2Po (  2P1, twice the core loss of each transformer). When V1 is regarded as shorted, the transformers are series connected across v2 and are short circuited no the side of primaries. Therefore the impedance seen at V2 is 2Z and when  V2 is adjustes to circulate full load current (If1), the power fed in is 2Pc ( twice the full load copper loss of each transformer). Thus in sumpner’s test  while transformers are not supplying any load, full load iron loss occurs in their cores and ull copper loss occurs in their windings net power input to the transformer being (2Po* 2Pc).
The heat run test could, therefore, be conducted on the two transformers, while only losses are supplied.



RESULT:


            Sumpner’s test is done on identical pair of 1 phase transformer from which the following are obtained.
The equivalent parameters are
1)      Ro 
2)      Xo
3)      Ro1
4)      Xo1
5)      Percentage efficiency 
6)      Percentage regulation (lag); Percentage regulation (lead)




Do not Delete prevent copying

Self Learners By Maniramakrishna

Popular Posts

Comments

Loom solar

Email subscribe

Enter your email address:

Delivered by FeedBurner

Loom solar 2