Xd and Xq of Alternator | Slip Test


Xd AND Xq OF A SALIENT POLE SYNCHRONOUS MACHINE.

AIM: To find Xd and Xq of a salient pole synchronous machine by slip test.

APPARATUS: 3 F Auto transformer 1 No.
                                    Ammeter (0-10A) MI. 1 No.
                                    Voltmeter (0-300V) MI. 1No.
                                    rheostats (296 ohm/ 2.8A), (45 ohm/ 5A)






PROCEDURE:
  1. Connections are made as per Circuit diagram.
  2. Switch on DC supply and run the DC motor at a speed below t he synchronous speed of alternator.
  3. Switch on AC supply and increase auto transformer out put to a suitable value note the variation in voltmeter and ammeter.
  4. For another speed take the similar readings.
  5. Adjust speed to get maximum oscillations in the ammeter and voltmeter.
  6. Note maximum and minimum readings of voltmeter and ammeter.
  7. Adjust the auto transformer output for a different value and take readings.
  8. Vary the speed to a value greater than synchronous speed and repeat the Experiment.
Observations:

N(rpm)
Imin(amps
Imax(amps)
Vmax(volts)
Vmin(volts)
Xd(ohms)
Xq(ohms)
Xd/Xq

















Precautions: Slip should be always be +/- 5%
Result:

THEORY (Determination of Xd & Xq – slip test)

            Direct  and quadrature axis reactances of a silent pole synchronous machine can be estimated by means of the test. The machine armature is connected to a 3-phase supply whose voltage is much less than the rated voltage of the machine. While the rotor is run at spee close to synchronous with the field winding fell open circuited. Since the excitation emf is zero, heavy current would be drawn by the armature, if connected to the r ated voltage supply.

            The currents drawn by armature set up an mmf wave rotating an synchronous speed. Since the rotor being run at a speed close to synchronous, the stator mmf moves slowly past the field poles at slip speed (Ns – N). When the stator mmf is alighned with the d-axis (field poles), flux fj / pole is setup. So that effective reactance offered by the machine is Xd. Similarly when the stator mmf aligns with the q=axis, the flux set up is fq/pole and the machine reactance is Xq. The current drawn by the armature therefore, varles cyclically at twice the slip frequency. The rmscurrent is minimum when machine reactance is Xd and is maximum when it is Xq. Because of cycle current variations and consequent voltage drop in the impedance of supply lines, the voltge at machine terminds also varies cyclically and has a mimimum value at maximum current and maximum value at mimimum current. The machine reactance can be found as

            Xd = (VE ( a1 Ia min) / (Ö3 Ia(min)
            Xq = (VE (at Ia max) / (Ö3 Ia (max)



For: Electrical Machines Lab Experiments Click below links








Monday, 20 January 2020

Electrical Machines Lab- PARALLEL OPERATION OF SINGLE PHASE TRANSFORMERS

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&

  Electrical And Electronics Engineering 



PARALLEL OPERATION OF SINGLE PHASE TRANSFORMERS





In modern power distribution systems it becomes inevitable to suffice the increasing load demand very often, in such cases where there is only one transformer connected to accomplish this work become insufficient, another transformer is brought into parallel operation, To maintain the economics and load sharing of these transformers knowledge of the load shared by this transformer becomes important. 


To bring parallel operation, it needs to satisfy a few set of rules such as,
Ø  Primary windings of the transformers should be suitable for the supply system voltage and frequency.
Ø  Polarity should be maintained
Ø  The voltage ratings of both primaries and secondaries should be identical, as such, transformation ratio.
Ø  The percentage impedances should be equal in magnitude and have the same X / R ratio in order to avoid circulating current and to operate at different power factors.
Ø  To avoid circulating currents, the equivalent impedances should be inversely proportional to the individual KVA ratings.




  👇👇👇👇Android Apps for Students 👇👇👇👇
  
Electrical Machines Nptel Notes


gate previous papers


ese previous papers 

nptel Electrical machines videos


nptel power electronics notes


Electrical Machines Lab -OC & SC TEST ON 1–PHASE TRANSFORMER.

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&


  Electrical And Electronics Engineering 



OC & SC TEST ON 1–PHASE TRANSFORMER.




The difficulties in testing of large transformers by direct loading 
(I) large amount of energy has to be wasted in such test
 (ii) it is a stupendous (impossible for large transformers) task to arrange a load large enough for direct loading. 


Electrical Machines Lab -BRAKE TEST ON 3 - Phase INDUCTION MOTOR

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&


  Electrical And Electronics Engineering 

BRAKE TEST ON 3 - F INDUCTION MOTOR


 Determination of performance characteristics of 3 - F induction motor by conducting brake test.


Electrical Machines Lab-SUMPNER’S TEST ON PAIR OF SINGLE PHASE TRANSFORMERS.

Electrical Machines Lab
for
 B.Tech / B.E /Diploma
&
  Electrical And Electronics Engineering 

SUMPNER’S TEST ON PAIR OF SINGLE PHASE TRANSFORMERS.




To perform sumpner’s test n  pair of identical 1- phase transformers to find the full load copper losses & iron losses of transformers.

 From test results calculate 
1) Equivalent parameters. 
2) Percentage Efficiency 
3) Percentage r egulation at given power factor & loads.

THEORY
            While OC and SC tests on a transformer gives its equivalent circuit parameters. These can not be used for the heat run test where the purpose is to determine the steady temperature rise if the transformer was fully loaded continuously this is so because under each of these tests the power loss to which the transformer is subjected is either the core loss or copper loss but not both. The way out of this impasse with out conducting an actual loading t est is sumpner’s test which can only be conducted simultaneously  on two identical transformers. In conducting the sumpner’s test  the primaries of the two transformers are connected in parallel across the rated voltage supply (V1), while the two secondaries are connect ed in phase opposition as in fig. Current at low voltage (V2) is injected in to secondaries to rated value.



for more ..........